BỘ LẬP TRÌNH PLC CPU K306EX-24AT VÀ K306EX-24AR
THÔNG SỐ KỸ THUẬT
|
|||
Performance Indexes
|
CPU306EX
|
||
K306EX-24AT
|
K306EX-24AR
|
||
CPU
|
16-bit industrial
|
||
Execution Speed
|
Typical Bool instruction time: <0.5 μS
Word operation time: <48μS
Arithmetic operation time for integers: <65μS
Arithmetic operation time for floating points: <150μS
|
||
DI Points
|
14XDC24V
|
||
DO Points
|
10XDC24V
|
10Xrelay
|
|
User Program Memory
|
FRAM, 32KB/about 4,000 steps
|
||
Program Backup
|
Permanent storage, without the need of battery
|
||
Memory Area
|
Variable storage area (V area): 4KB
System storage area (SM area): 300 bytes
Internal storage area (M area): 32 bytes
|
||
Data Retention Characteristic
|
Configure with the programming software: V area, C (counter) area
|
||
Retention Mode and Period
|
Adopt super capacitors and support a retention period of not less than 144 hours upon power failure under normal temperature.
|
||
Data Backup Characteristic
|
Perform backup operations VB3648~VB3902 according to user instructions, 255 bytes in total
|
||
Backup Mode and Time
|
FRAM, 255 bytes in total (writing operation for 10 billion times), permanent backup
|
||
Floating Points
|
Supported; the whole V area can be used for floating points
|
||
Programming Language Supported
|
Ladder Drawing (LD), Instruction List (IL)
|
||
Instruction Set
|
Basic instructions: 114; expansion instructions: 420
|
||
Password Protection
|
Yes
|
||
Max. I/O
|
Digital data: 280 in total (256 DI and 256 DO respectively);
Analog data: 60 in total (32AI and 32 AO respectively)
|
||
Counter
|
256
|
||
Operation Mode of Counter
|
Addition, subtraction
|
||
Counter Range
|
-32768~32767
|
||
Counting Value Retention Function
|
Yes
|
||
Timer
|
256
1 ms time base: 4
10 ms time base: 16
100 ms time base: 236
|
||
High-speed Counter
|
6 high-speed counters
where, single-phase counters: 6, with a maximum frequency of 30 KHz
where, dual-phase counters: 4, with a maximum frequency of 20 KHz
|
||
Pulse Output
|
2, PTO (Pulse Train Output)/PWM (Pulse Width Modulation output);
Maximum output frequency: 20 KHz
|
||
Analog Potentiometer
|
2, 10-bit resolution, values corresponding to internal registers
|
||
Interruption Function
|
Timing interruption: 2, 1ms resolution;
Timer interruption: T2/T3, 1ms resolution;
Edge interruption: 4, rising edge or falling edge optional;
High-speed interruption, communication interruption
|
||
Real-time Clock
|
Yes, with an error not greater than 2 minutes/month under a temperature of 25°C
The user can use the software to set/read: year, month, day, hour, minute, second, week. Adopt super capacitors and support a retention period of not less than 144 hours upon power failure under normal temperature.
|
||
Number of Connectable Expansion Modules
|
15; regardless of types
|
||
COM Port
|
2, RS232 or RS485;
Supported working modes: Programming,
Modbus-RTU (master/slave), Free protocol
|
||
Equipment Connected with COM Port
|
RS232/RS485: PC (for programming), third-party HMI panel, third-party serial communication equipment (for example, instruments, bar code reader, etc.)
|
||
Input Power Supply
|
AC85~265V
|
||
Sensor Load Power Supply
|
DC24V, max. 500 mA
|
||
Dimensions (L*W*H)
|
125X114X70mm
|